Product Description

CT-ERS.12S 1SVR730100R3100 time relay is a single-function electronic time relay in the CT-S timer family. It provides a turn-on delay (turn-on delay) function with a time range of 0.05 seconds to 300 hours, a total of 10. This time relay has A rated control supply voltage of 24-48 V DC / 24-240 V AC and an output rating of 250 V / 4 A, with a sealable transparent cover that protects against unauthorized changes. The device adopts the screw connection technology of double cavity cage connecting terminal.


Electronic time relay for emergency switchboard CT-S series (CT-ERS.12S, on-delay time relay: 0,05s -300h, A1-A2: AC 24-240V, 50/60Hz, A1-A2: DC 24-48V; code: 1063 A1 00000460004A)





image.png


Go to part:


Ordering information

Popular Downloads

dimension

Technical parameter

UL/CSA Technical specifications

Environmental condition

Material Compliance

ABB EcoSolutions

Certification and Declaration (Document coding)

Packaging information

External classifications and standards

Ordering information

European Item Number (EAN):

4016779851459

Minimum order quantity:

1 piece

Customs Tariff Number:

85364900

Popular Downloads

Data sheet, technical data:

2CDC110004C0210_01

Instructions and manuals:

1SVC730050M1000

1SVC730050M0000

CAD Dimensional Drawing:

2CDC001079B0201

dimension

Product net width:

22.5mm

Product net height:

85.6 mm

Product depth:

103.7mm

Product net weight:

0.106 kg

Technical parameter

Timer relay Type:

ON-Delay

Time scale:

0.05 s... 300 h

Rated control supply voltage (Us):

24... 240 V AC

24... 48 V DC

Rated operating voltage:

Auxiliary Circuit 250 V

Rated frequency (f):

50 / 60 Hz

DC

Output:

1 c/o (SPDT) contact

Terminal type:

Screw Terminals

Rated operating current AC-12 (Ie):

(230 V) 4 A

Rated operating current AC-15 (Ie):

(230 V) 3 A

Rated working current DC-12 (Ie):

(24 V) 4 A

Rated working current DC-13 (Ie):

(24 V) 2 A

Minimum switching capacity:

12 V

100 mA

Rated impulse withstand voltage (Uimp):

Input Circuit 4 kV

Output Circuit 1 / Output Circuit 2 4 kV

Rated insulation voltage (Ui):

Input Circuit / Output Circuit 500 V

Output Circuit 1 / Output Circuit 2 300 V

Protection level:

Housing IP50

Terminals IP20

Overvoltage category:

III

Pollution level:

3

Short circuit protection equipment:

Output Circuit NC - F Type Fuses 6 A

Output Circuit NO - F Type Fuses 10 A

Electrical life:

AC-12 100000 cycle

Mechanical life:

Nr. Operations 30000000 cycle

Connection capacity:

Flexible with Ferrule 1x 0.5... 2.5 mm²

Flexible with Ferrule 2x 0.5... 1.5 mm²

Flexible with Insulated Ferrule 1x 0.5... 2.5 mm²

Flexible with Insulated Ferrule 2x 0.5... 1.5 mm²

Flexible 1x 0.5... 2.5 mm²

Flexible 2x 0.5... 1.5 mm²

Rigid 1x 0.5... 4 mm²

Rigid 2x 0.5... 2.5 mm²

Tightening torque:

0.6... 0.8 N·m

Strip length:

8 mm

Recommended screwdriver:

0.8 x 4

4.5

Pozidriv 1

Installation position:

one 6

Mount to DIN rail:

TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715

TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715

Standard:

CAN/CSA C22.2 No.14

IEC/EN 63000

IEC/EN 61812-1

UL 508

UL/CSA Technical specifications

Maximum operating voltage UL/CSA:

Output Circuit 300 V AC

Contact Grade UL/CSA:

B300

Connection Capacity UL/CSA:

Flexible 1x 18-14 AWG

Flexible 2x 18-16 AWG

Rigid 1x 20-12 AWG

Rigid 2x 20-14 AWG

Tightening torque UL/CSA:

7.08 in·lb

The guide power of the contact element complies with UL508 standards:

B300

Flammability according to UL94 standard:

V-0